Refine your search:     
Report No.
 - 

Secondary sodium fire measures in JSFR

Chikazawa, Yoshitaka  ; Kato, Atsushi*; Yamamoto, Tomohiko  ; Kubo, Shigenobu ; Ohno, Shuji  ; Iwasaki, Mikinori*; Hara, Hiroyuki*; Shimakawa, Yoshio*; Sakaba, Hiroshi*

JSFR adopts double boundary for all sodium components. However, design measures are investigated for the secondary sodium fire inside the reactor building, which might be assumed as design extension conditions (DECs). Candidates of sodium fire measures in the secondary sodium systems such as sodium drain, nitrogen injection, pressure release valve, catch pan and leak sodium drain system have been compared from the view point of safety. Wide range of sodium fires in the steam generator room and air cooler have been analyzed evaluating performances of the candidate sodium fire measures.