Sodium pooI combustion Test (Run-F7-3 and Run-F8-1) to confirm the condition of floor liner's corrosion

not registered  ; not registered ; Ohno, Shuji  ; not registered  

Small-scale sodium pool combustion tests Run-F7-3 and Run-F8-1 were performed to investigate the corrosion of floor liner under high moisture condition. ln the both tests, which were performed using the 3m$$^{3}$$ FRAT-1 vessel at the SAPFIRE facility, the sodium of 507deg-C was leaked on the carbon steel catch pan about for 25 minutes with the flow rate of around 25 kg/h. The air in the vessel was ventilated with the flow rate of 5m$$^{3}$$/min containing the moisture of 25000-28000 vol.ppm. The duration of combustion was different in two tests by changing the starting time of argon gas injection into the vessel. As the results of post-test analysis such as observation of catch pan surface and chemical analysis of the deposits, it was confirmed that 'Na-Fe double oxidization type corrosion' was dominant in the both tests and that the catch pan and deposits were not under the condition leading to the occurrence of 'molten salt type corrosion.'