MK-III Performance Tests in JOYO; Transient Response Tests

Kawahara, Hirotaka ; Rekimoto, Masafumi ; Jo, Takahisa; Ishida, Koichi; Ariyoshi, Masahiko; Isozaki, Kazunori 

The manual shutdown tests and loss of electric power supply tests were carried out as the transient response test on anomaly condition at 70MWt and 140MWt operation. The decay heat removal tests by main cooling system were carried out after each transient response tests. It was confirmed that the plant protection system operates properly and the reactor can be shut down safely. These results confirmed that the thermal transients are less severe than the design conditions.