Refine your search:     
Report No.
 - 

Water chemistry control in HTTR

Sekita, Kenji; Furusawa, Takayuki ; Emori, Koichi; Ishii, Taro*; Kuroha, Misao; Hayakawa, Masato; Ouchi, Hiroshi

A carbon steel used is used for the main material for the components and pipings of the pressurized water cooling system etc. that are the reactor cooling system of the HTTR. Water quality is managed by using the hydrazine in the coolant of the water cooling system to prevent corrosion of the components and deoxidize the coolant. Also, regular analysis is carried out for the confirmation of the water quality. The following results were obtained through the water quality analysis. (1) In the pressurized water cooling system, the coolant temperature rises higher due to the heat removal of the primary coolant. So, the ammonia was formed in the thermal decomposition of the hydrazine. The electric conductivity increased, while the concentration of the hydrazine decreased, there was no problem as the plan it. (2) Thermal decomposition of the hydrazine was not occurred in the auxiliary water cooling system and vessel cooling system because of the coolant temperature was low. (3) An indistinct procedure is clarified and procedure of water quality analysis was established in the HTTR. (4) It is assumed that the corrosion of the components in these water cooling system hardly occurred from measurement results of dissolved oxide and chloride ion. Thus, the water quality was managed enough.