Standard guideline for the seismic response analysis method using three-dimensional finite element model of reactor buildings (Contract research) (Translated document)
Choi, B. ; Nishida, Akemi ; Kawata, Manabu; Shiomi, Tadahiko; Li, Y.
In the assessment of seismic safety and the design of building structures in nuclear facilities, lumped mass models have been used as standard methods. Recent advances in computer capabilities allow the use of three-dimensional finite element (3D FE) models to account for the 3D behavior of buildings, material nonlinearity, and the nonlinear soil-structure interaction effect. While 3D analysis method has many advantages, it is necessary to ensure its reliability as a new approach. The International Atomic Energy Agency performed an international benchmark study using the 3D FE analysis model for reactor building of Unit 7 at TEPCO's Kashiwazaki-Kariwa Nuclear Power Station based on recordings from the Niigataken Chuetsu-oki Earthquake in 2007. Multiple organizations from different countries participated in this study and the variation in their analytical results was significant, indicating an urgent need to improve the reliability of the analytical results by standardization of the analytical methods using 3D FE models. Additionally, it has been pointed out that it is necessary to understand the 3D behavior in the seismic fragility assessment of buildings and equipment, using realistic seismic response analysis method based on 3D FE models. In view of these considerations, a guideline for the seismic response analysis method using a 3D FE model was developed by incorporating the latest knowledge and findings in this area. The purpose of the guideline is to improve the reliability of the seismic response analysis method using 3D FE model of reactor buildings. The guideline consists of a main body, commentaries, and appendixes. The standard procedures, recommendations, key points to note, and technological bases for conducting seismic response analysis on reactor buildings using 3D FE models are provided in the guideline. In addition, the guideline will be revised reflecting the latest knowledge.