Handling of HTTR second driver fuel elements in assembling and storage working

Tomimoto, Hiroshi; Kato, Yasushi; Owada, Hiroyuki; Sato, Nao; Shimazaki, Yosuke; Kozawa, Takayuki; Shinohara, Masanori; Hamamoto, Shimpei; Tochio, Daisuke; Nojiri, Naoki; et al.

JAEA-Technology 2009-025, 29 Pages, 2009/06

JAEA-Technology-2009-025.pdf:21.78MB

The first driver fuel of the HTTR (High Temperature Engineering test Reactor) was loaded in 1998 and the HTTR reached first criticality state in the same year. The HTTR has been operated using the first driver fuel for a decade. In Fuel elements assembling, 4770 of fuel rods which consist of 12 kinds of enrichment uranium are loaded into 150 fuel graphite blocks for HTTR second driver fuel elements. Measures of prevention of fuel rod miss loading, are employed in fuel design. Additionally, precaution of fuel handling on assembling are considered. Reception of fuel rods, assembling of fuel elements and storage of second driver fuels in the fresh fuel storage rack in the HTTR were started since June, 2008. Assembling, storage and pre-service inspection were divided into three parts. The second driver fuel assembling was completed in September, 2008. This report describes concerns of fuel handling on assembling and storage work for the HTTR fuel elements.

JAEA Reports

Maintenance of the auxiliary component cooling water system and the general cooling water system in HTTR

Kameyama, Yasuhiko; Watanabe, Shuji; Inoi, Hiroyuki; Shimizu, Yasunori; Aragaki, Etsushi; Shinozaki, Masayuki; Ota, Yukimaru

JAEA-Testing 2008-001, 63 Pages, 2008/03

JAEA-Testing-2008-001.pdf:20.97MB

The High Temperature Engineering Test Reactor (HTTR) has the Auxiliary Component Cooling Water System (ACCWS) and the General Cooling Water System (GCWS). ACCWS supplies the cooling water to the many facilities those are necessary to operate and cool the reactor. GCWS supplies the cooling water to the many facilities those are necessary to operate and cool the reactor in normal circumstances. Two kinds of the cooling water are cooled with the Cooling Tower. Each facility has the circulation pump, the cooling tower, the piping, the valve, the strainer and the injection system of the chemical solution. And these two facilities are operating all the year. This report describes maintenance items, improvements and management of the ACCWS and the GCWS.

JAEA Reports

Evaluation of heat exchange performance for the auxiliary component cooling water system cooling tower in HTTR

Tochio, Daisuke; Kameyama, Yasuhiko; Shimizu, Atsushi; Inoi, Hiroyuki; Yamazaki, Kazunori; Shimizu, Yasunori; Aragaki, Etsushi; Ota, Yukimaru; Fujimoto, Nozomu

JAEA-Technology 2006-045, 43 Pages, 2006/09

JAEA-Technology-2006-045.pdf:5.97MB

The auxiliary component cooling water system (ACCWS) is one of the cooling system in High Temperature Engineering Test Reactor (HTTR) The ACCWS has the features not only many facilities cooling but also heat sink of the vessel cooling system which is one of the engineering safety features. Therefore, the ACCWS is required to satisfy the design criteria of heat removal performance. In this report, heat exchange performance data of the rise-to-power-up test and the in-service operation for the ACCWS cooling tower was evaluated. Moreover, the evaluated values were compared with the design values, and it is confirmed that ACCWS cooling tower has the required heat exchange performance in the design.