Design and safety assessment of cooling facilities for air system

Asano, Norikazu; Nishimura, Arashi; Takabe, Yugo; Araki, Daisuke; Yanai, Tomohiro; Ebisawa, Hiroyuki; Ogasawara, Yasushi; Oto, Tsutomu; Otsuka, Kaoru; Otsuka, Noriaki; et al.

JAEA-Technology 2021-045, 137 Pages, 2022/06

JAEA-Technology-2021-045.pdf:2.97MB

A collapse event of a cooling tower for secondary cooling system in the Japan Materials Testing Reactor (JMTR) was caused by the strong winds of Typhoon No.15 on September 9, 2019. As measures against the event, the working group for the renewal of the UCL (Utility Cooling Loop) cooling tower was established in the department of JMTR, and the integrity of the UCL cooling tower, which is the same type of wooden cooling tower as the secondary cooling tower in the JMTR, was investigated. As a result of this investigation, we have decided to replace the existing UCL cooling tower with a new cooling system. After investigations, in order to reduce the risk of collapse due to wood decay, the new cooling system was installed as a component of the air system to be managed as a performance maintenance facility after decommissioning. This report describes the design of and the evaluation results of the facility.

JAEA Reports

Investigation on integrity of heat exchanger and tanks in primary cooling system of JMTR

Onoue, Ryuji; Ebisawa, Hiroyuki; Fukasaku, Akitomi; Kusunoki, Tsuyoshi

JAEA-Review 2010-059, 19 Pages, 2010/12

JAEA-Review-2010-059.pdf:4.07MB

The JMTR is a light water moderated and cooled tank-type reactor. First criticality was achieved in March 1968. The refurbishment of JMTR is scheduled from the beginning of FY2007 to the end of FY2010. An investigation on aged components was carried out since the beginning of FY2007. In this paper, the aged-investigations for heat exchangers and tanks in the primary cooling system are presented. The integrity of three heat exchangers was confirmed by the eddy current testing for heat exchanger tubes, visual observation using endoscope, liquid penetration test of tube plates and thickness measurement of the main body. The visual inspection test and liquid penetration test were carried out to confirm the integrity of tanks in the primary cooling system. The heat exchangers and tanks in the primary cooling system will be continuously used in the future operation of the JMTR by appropriate maintenance activities based on the long-term maintenance program.

JAEA Reports

Investigation on integrity of the surge tank, the degas tank and the purify water tank for the primary cooling system of JMTR

Nemoto, Hiroyoshi; Ebisawa, Hiroyuki; Ogasawara, Yasushi; Echigoya, Shinichi

JAEA-Review 2010-018, 32 Pages, 2010/07

JAEA-Review-2010-018.pdf:2.07MB

An integrity investigation was carried out for the JMTR reactor installations, which were the primary cooling system tanks (the surge tank, the degas tank and the purify water tank) and they would be used for the long term after JMTR restart, before the renewal work for the JMTR on FY2007. The visual inspection and the liquid penetrate test (PT) were carried out as the integrity investigation to confirm the integrity of primary cooling system tanks. In order to use the surge tank, the degas tank and the purify water tank continuously for long term, it is important for maintaining the integrity of the surge tank, the degas tank and the purify water tank by the periodical maintenance and the repairing work.

JAEA Reports

Investigation on integrity of JMTR concrete structures, cooling system and utility facilities

Ebisawa, Hiroyuki; Tobita, Kenji; Fukasaku, Akitomi; Kaminaga, Masanori

JAEA-Review 2009-055, 24 Pages, 2010/02

JAEA-Review-2009-055.pdf:7.08MB

The condition of facilities and components to be used for re-operation of the Japan Materials Testing Reactor (JMTR) from FY2011, was investigated before the refurbishment work. An investigation of aged components (aged-investigation) was carried out for concrete structures of the JMTR reactor building, exhaust stack, trench, canal, filter banks and for aged components of tanks in the primary cooling system, heat exchangers, pipes in the secondary cooling system, cooling tower, emergency generators and so on, in order to identify their integrity. The aged-investigation was carried out from the beginning of FY2007. As a result, cracks of concrete structures such as the exhaust stack, a foundation of the UCL (Utility Cooling Line) elevated water tank were repaired and pipe linings of secondary cooling system were replaced. Motors of primary cooling pumps, pumps in the secondary cooling system and in other systems were decided to replace from viewpoints of future maintenance and improvement of reliability. Other components and the reactor building were decided to use continuously for a long-term by appropriate maintenance activities based on the long-term maintenance plan. In this paper, the aged-investigation for the JMTR reactor building, heat exchangers and emergency generators is presented.

JAEA Reports

The Outline of investigation on integrity of JMTR concrete structures, cooling system and utility facilities

Ebisawa, Hiroyuki; Hanakawa, Hiroki; Asano, Norikazu; Kusunoki, Hidehiko; Yanai, Tomohiro; Sato, Shinichi; Miyauchi, Masaru; Oto, Tsutomu; Kimura, Tadashi; Kawamata, Takanori; et al.

JAEA-Technology 2009-030, 165 Pages, 2009/07

JAEA-Technology-2009-030.pdf:69.18MB

The condition of facilities and machinery used continuously were investigated before the renewal work of JMTR on FY 2007. The subjects of investigation were reactor building, primary cooling system tanks, secondary cooling system piping and tower, emergency generator and so on. As the result, it was confirmed that some facilities and machinery were necessary to repair and others were used continuously for long term by maintaining on the long-term maintenance plan. JMTR is planed to renew by the result of this investigation.

Journal Articles

Renewal of the reactor facilities for JMTR

Gorai, Shigeru; Hanawa, Yoshio; Ebisawa, Hiroyuki; Oto, Tsutomu; Fukasaku, Akitomi

UTNL-R-0466, p.1_2_1 - 1_2_8, 2008/03

no abstracts in English

Journal Articles

Progress in development of edge Thomson scattering system for ITER

Hatae, Takaki; Nakatsuka, Masahiro*; Yoshida, Hidetsugu*; Ebisawa, Katsuyuki*; Kusama, Yoshinori; Sato, Kazuyoshi; Katsunuma, Atsushi*; Kubomura, Hiroyuki*; Shinobu, Katsuya*

Fusion Science and Technology, 51(2T), p.58 - 61, 2007/02

 Times Cited Count:6 Percentile:42.5(Nuclear Science & Technology)

no abstracts in English

JAEA Reports

User's manual of a computer code for evaluating effectiveness of seismic component base isolation, EBISA; Function of dynamic response analysis code

Tsutsumi, Hideaki*; Sugino, Hideharu*; Onizawa, Kunio; Mori, Kazunari*; Yamada, Hiroyuki*; Shibata, Katsuyuki; Ebisawa, Katsumi*

JAEA-Data/Code 2006-004, 167 Pages, 2006/03

JAEA-Data-Code-2006-004.pdf:6.41MB

EBISA (Equipment Base Isolation System Analysis) code evaluates the effectiveness of seismic isolation for the important components in the seismic safety, and consists of the three codes, probabilistic seismic hazard code (SHEAT), seismic dynamic response analysis code (RESP) and seismic failure probability and frequency evaluation code. In these codes, RESP code is used for the calculation of the dynamic response behavior of a nuclear component with seismic isolation devices. This report describes the overall explanation of EBISA, and user's guide of RESP code including the analysis function, input manual and sample problem.

JAEA Reports

Examination on detaching method of an irradiated mock-up with Li$$_{2}$$TiO$$_{3}$$ pebble bed from the core of JMTR

Ikeshima, Yoshiaki; Ishida, Takuya*; Tsuchiya, Kunihiko; Tomita, Kenji; Ebisawa, Hiroyuki; Magome, Hirokatsu; Nakamichi, Masaru*; Kitajima, Toshio; Kawamura, Hiroshi

JAERI-Tech 2005-005, 37 Pages, 2005/02

JAERI-Tech-2005-005.pdf:7.59MB

no abstracts in English

Journal Articles

Design and evaluation methodology for seismic base isolation of nuclear components by probabilistic approach

Tsutsumi, Hideaki*; Ebisawa, Katsumi*; Yamada, Hiroyuki*; Shibata, Katsuyuki; Fujimoto, Shigeru*

Nihon Zairyo Gakkai JCOSSAR 2003 Rombunshu, p.829 - 836, 2003/11

no abstracts in English

JAEA Reports

SHEAT for PC: A Computer code for probabilistic seismic hazard analysis for personal computer, user's manual

Yamada, Hiroyuki; Tsutsumi, Hideaki*; Ebisawa, Katsumi*; Suzuki, Masahide

JAERI-Data/Code 2002-001, 161 Pages, 2002/03

JAERI-Data-Code-2002-001.pdf:6.62MB

no abstracts in English

JAEA Reports

Study on the dynamic response analysis for evaluating the effectiveness of base isolation for nuclear components

Mori, Kazunari*; Tsutsumi, Hideaki*; Yamada, Hiroyuki; Ebisawa, Katsumi; Shibata, Katsuyuki

JAERI-Tech 2001-037, 85 Pages, 2001/06

JAERI-Tech-2001-037.pdf:6.27MB

no abstracts in English

JAEA Reports

Shaking table test and dynamic response analysis of 3-D component base isolation system using multi-layer rubber bearings and coil springs

Tsutsumi, Hideaki*; Yamada, Hiroyuki; Ebisawa, Katsumi; Shibata, Katsuyuki; Fujimoto, Shigeru*

JAERI-Tech 2001-033, 124 Pages, 2001/06

JAERI-Tech-2001-033.pdf:9.98MB

no abstracts in English

JAEA Reports

Earthquake observation database in JAERI Oarai site obtained by vertical instrument arrays from 1987-2000

Ebisawa, Katsumi; Yamada, Hiroyuki; Tsutsumi, Hideaki*; Shibata, Katsuyuki; Ando, Kazuhiro*; Baba, Osamu; Suzuki, Hideyuki

JAERI-Data/Code 2001-009, 96 Pages, 2001/03

JAERI-Data-Code-2001-009.pdf:4.14MB

no abstracts in English

JAEA Reports

Characteristics and dynamic response analysis of 3-D component base isolation system using ball bearings and air springs

Tsutsumi, Hideaki*; Yamada, Hiroyuki; Mori, Kazunari*; Ebisawa, Katsumi; Shibata, Katsuyuki

JAERI-Tech 2000-086, 93 Pages, 2001/02

JAERI-Tech-2000-086.pdf:6.56MB

no abstracts in English

Journal Articles

Development of seismic emergency information system adaptable to disaster management spatial information system

Ebisawa, Katsumi; Kuno, Tetsuya; Shibata, Katsuyuki; Abe, Ichiro*; Kakumoto, Shigeru*; Kameda, Hiroyuki*

Chiiki Anzen Gakkai Kogaishu, 10, p.133 - 136, 2000/11

no abstracts in English

Journal Articles

Dynamic behavior and base isolation effect of three dimensional base isolation test system for nuclear components

Tsutsumi, Hideaki*; Yamada, Hiroyuki; Ebisawa, Katsumi; Shibata, Katsuyuki; Fujimoto, Shigeru*

Doboku Gakkai Dai-2-Kai Menshin, Seishin Korokiumu Koen Rombunshu, p.75 - 82, 2000/11

no abstracts in English

JAEA Reports

Characteristics and dynamic resonse analysis of 3-D component base isolation system using multi-layer-rubber-bearings and coil springs

Tsutsumi, Hideaki*; Yamada, Hiroyuki; Ebisawa, Katsumi; Shibata, Katsuyuki

JAERI-Tech 2000-045, 107 Pages, 2000/07

JAERI-Tech-2000-045.pdf:7.25MB

no abstracts in English

Journal Articles

Dynamic response of base isolation test system for nuclear components under natural seismic motion

Tsutsumi, Hideaki*; Yamada, Hiroyuki; Teragaki, Toshio*; Ebisawa, Katsumi; Shibata, Katsuyuki

Seismic Engineering 2000 (PVP-Vol.402-1), p.141 - 146, 2000/00

no abstracts in English

Oral presentation

Refurbishment and restart of JMTR, 3; Investigation of integrity of reactor facilities, 2; Primary cooling system heat exchanger and tanks

Koike, Sumio; Onoue, Ryuji; Ebisawa, Hiroyuki; Nemoto, Hiroyoshi; Takahashi, Kunihiro; Kaminaga, Masanori

no journal, , 

no abstracts in English

23 (Records 1-20 displayed on this page)