Integrity check of emergency generator for the HTTR after the Tohoku-Pacific Ocean Earthquake

Homma, Fumitaka; Inoi, Hiroyuki; Watanabe, Shuji; Fukutani, Koji*

JAEA-Technology 2013-034, 57 Pages, 2013/12

JAEA-Technology-2013-034.pdf:11.01MB

Emergency generator of HTTR started in the blackout occurred just after an Tohoku Pacific Ocean Earthquake on March 11, 2011 with an intensity of 5 upper on the Japanese seven stage seismic scale and its duration time was long. In addition, we suffer from multiple severe aftershocks just after the start of emergency generators. Emergency generator of HTTR was able to supply output electric power sufficiently and stably to required loads. We carried on integrity check of the emergency generator for the HTTR after the earthquake. In particular, we put emphasis on finding faults caused by thee earthquake shaking. As a result, we found that the erosion in a combustion liner, and the condition of erosion was very strange and rare. Therefore, we carried out investigations of causes of erosion, and change of specifications for combustion liner to prevent erosion. This measure improve the reliability for the further Large-Scale earthquake.