Asazuma, Shinichiro; Okada, Takashi; Kashiro, Kashio; Matsumoto, Masaki; Nakata, Keiji*; Gonnokami, Kiyomi*; Toda, Rikiya*
JNC TN8430 2003-011, 56 Pages, 2004/01
The glove-box dismantling facility in the Plutonium Fuel Production Facility is developed to dismantle after-service glove-boxes with remote-controlled devices such as an arm-type manipulator. An abrasive wheel cutter, which is used to size reduce the gloveboxes, generates sparks during operation. This dispersing spark was a problem from the fire prevention point of view. A suitable spark control measures for this operation were required. We developed panels to minimize spark dispersion, shields to prevent the income of sparks to the pre-filter, and incombustible pre-filters. The equipment was tested and effectiveness was confirmed. This report provides the results of these tests.