Conclusive Experimental Study of Prevention Measures Against Sodium Combustion Residuum Reignition; Run-F9-1, Run-F9-2
Ishikawa, Hiroyasu ; Ohno, Shuji ; Miyahara, Shinya
Nitrogen gas can be an extinguisher or a mitigating material in the case of sodium leak and fire accident in an air atmosphere, which may occur at a liquid metal cooled nuclear power plant. However, sodium combustion residuum sometimes reignites in the air atmosphere even at room temperature when it was produced by nitrogen gas injection to the burning sodium. Then, in this study we executed conclusive experiments of prevention measures against sodium combustion residuum reignition by a mixture of carbon-dioxide (C0 sub2) gas, humidity and nitrogen gas. The experiments were carried out with the FRAT-1 test equipment; the humidity conditions were changed in air which were used to sodium combustion atmosphere and exposure air for confirmation of prevented combustion residue reignition. First of all, the sodium of about 2.5kg was leaked in air atmosphere, and next, the sodium combustion was stopped by nitrogen gas injection. Next, the combustion residuum was cooled in the nitrogen atmosphere, and then the combustion residuum was exposed to atmosphere of carbon-dioxide (4%); humidity (6000vppm); oxygen (3%)-nitrogen (based gas) mixture. It was confirmed that the combustion residuum was not reignition even if exposed to the air atmosphere again at the end of experiment. We had confirmed that the prevention measures against sodium combustion residuum reignition to establish by this research were effective.