First switching network unit for the JT-60SA superconducting central solenoid

JT-60SA超伝導セントラルソレノイド用スイッチングネットワークユニットプロトタイプ

Lampasi, A.*; Zito, P.*; Coletti, A.*; Novello, L.*; 松川 誠; 島田 勝弘; Burini, F.*; Kuate-Fone, Y.*; Taddia, G.*; Tenconi, S.*

Lampasi, A.*; Zito, P.*; Coletti, A.*; Novello, L.*; Matsukawa, Makoto; Shimada, Katsuhiro; Burini, F.*; Kuate-Fone, Y.*; Taddia, G.*; Tenconi, S.*

In JT-60SA, the first SNU (prototype), consisting of six cubicles, was assembled in 2013. The factory tests on this system, including tests at full current and voltage, are being performed throughout 2014. The manufacturing of the remaining three SNUs will proceed after the success of such tests. The main characteristics of the developed SNU are; (1) Snchronized use of an electronic static circuit breaker (SCB) in parallel with an electromechanical bypass switch (BPS), (2) Nominal voltage of 5 kV, with a specific circuit to limit the transient voltage to 5.5 kV, (3) DC current interruption up to 20 kA, (4) Light BPS with opening and closing times shorter than 15 ms and 65 ms, respectively, (5) Breakdown resistance adaptable from 0.25 $$Omega$$ to 3.75 $$Omega$$ by four selectors, (7) Fully electronic making switch (MS) and (8) Breakdown resistors that could dissipate much more than 90 MJ.

Access

:

- Accesses

InCites™

:

パーセンタイル:64.63

分野:Nuclear Science & Technology

Altmetrics

:

[CLARIVATE ANALYTICS], [WEB OF SCIENCE], [HIGHLY CITED PAPER & CUP LOGO] and [HOT PAPER & FIRE LOGO] are trademarks of Clarivate Analytics, and/or its affiliated company or companies, and used herein by permission and/or license.